Voltage drop calculator: volts and per cent

The calculator needs JavaScript. The worked example, formula and figures below show exactly how it works, so you can do the sum yourself. A guide, not advice. Check your supplier's or maker's figures before ordering.

Short answer

Worked example

Worked example inputs
You enterValue
SupplySingle phase
Design current20 A
Cable length25 m
Cable size2.5 mm²
mV/A/m from the cable maker's data or BS 767118 mV/A/m
What the circuit suppliesOther uses
Voltage drop limit5 %
Supply voltage230 V

Voltage drop: 9.00 V (3.91%)

  • Within the guidance Voltage drop: 3.913 % UK-wide: BS 7671:2018+A4:2026 Appendix 12. Check with the source
Worked example results
ResultValue
Voltage drop9 V
As a share of the supply3.91%
Longest run within the limit31.94 m
mV/A/m used18 mV/A/m
Show the working
  1. mV/A/m: 18 (your figure)
  2. Voltage drop: 18 × 20 A × 25 m ÷ 1000 = 9 V
  3. As a share: 9 ÷ 230 V × 100 = 3.91%
  4. Longest run: 11.5 V × 1000 ÷ (18 × 20) = 31.9 m

How it works

  1. Voltage drop (V) = mV/A/m × design current Ib (A) × one-way length (m) ÷ 1000
  2. As a percentage = voltage drop ÷ supply voltage × 100
  3. Longest run = (limit % × supply voltage ÷ 100) × 1000 ÷ (mV/A/m × Ib)

Tabulated mV/A/m figures assume the conductor is at its maximum operating temperature, so this is on the safe side for most circuits.

Indicative only: an electrician checks the design against BS 7671 and the cable maker's data.

Our default (adjustable)

These are typical planning figures and our own allowances, not facts about your product. Change any of them in the calculator to match your bag, pack or tin.

FigureOur default (adjustable)KindSource
Supply voltage: Single phase230 VOur assumption
Not yet checked against the source
Our choice: change it to suit your job
UK nominal single-phase supply voltage (brief v2 E2). Researcher to cite the statutory source.
Supply voltage: Three phase400 VOur assumption
Not yet checked against the source
Our choice: change it to suit your job
UK nominal three-phase line voltage (brief v2 E2). Researcher to cite the statutory source.
Voltage drop limit: Lighting3 %Regulation or HSE figure
BS 7671:2018+A4:2026 Appendix 12 (lighting)
Not yet checked against the source
Source to be added by the Researcher
Brief v2 E2. Researcher to confirm against A4:2026.
Voltage drop limit: Other uses5 %Regulation or HSE figure
BS 7671:2018+A4:2026 Appendix 12 (other uses)
Not yet checked against the source
Source to be added by the Researcher
Brief v2 E2. Researcher to confirm against A4:2026.

Regulations and standards

  • BS 7671:2018+A4:2026 Appendix 4 (voltage drop, mV/A/m)
  • BS 7671:2018+A4:2026 Appendix 12 (voltage drop limits)

Explained: BS 7671 (the IET Wiring Regulations), Approved Document P (electrical safety).

BS 7671 is used across the UK. Who may do the work differs: Part P applies in England and Wales; Scotland and Northern Ireland have their own rules.

Reference tables this calculator reads
TableClauseNationsStatus
Voltage drop (mV/A/m) for flat twin and earth cableBS 7671:2018+A4:2026 Appendix 4, Table 4D5UK-wide0/7 values entered
Not yet checked against the source

What to buy

FAQs