U-value calculator

The calculator needs JavaScript. The worked example, formula and figures below show exactly how it works, so you can do the sum yourself. A guide, not advice. Check your supplier's or maker's figures before ordering.

Short answer

Worked example

Worked example inputs
You enterValue
ElementWall
The workNew element in an existing home (e.g. an extension)
Where the home isEngland
Build-up, inside to outsideBrick: material Brick (outer leaf), thickness 103 mm, thermal conductivity λ 0.77 W/mK, studs or joists run through this layer No; PIR: material PIR insulation board, thickness 100 mm, thermal conductivity λ 0.022 W/mK, studs or joists run through this layer No; Aircrete block: material Aircrete block, thickness 100 mm, thermal conductivity λ 0.15 W/mK, studs or joists run through this layer No; Plaster: material Gypsum plaster, thickness 13 mm, thermal conductivity λ 0.57 W/mK, studs or joists run through this layer No
Inside surface resistance Rsi0.13 m²K/W
Outside surface resistance Rse0.04 m²K/W

U-value: 0.181 W/m²K

  • Outside the guidance U-value vs the Part L limit: 0.181 W/m²K England: Approved Document L 2021 Vol 1, Table 4.2 (new elements in existing dwellings). Check with the source
Worked example results
ResultValue
U-value0.181 W/m²K
Total resistance5.538 m²K/W
Part L limit for this work0.18 W/m²K
Each layer
LayerThicknessλR
Brick103 mm0.77 W/mK0.133 m²K/W
PIR100 mm0.022 W/mK4.545 m²K/W
Aircrete block100 mm0.15 W/mK0.667 m²K/W
Plaster13 mm0.57 W/mK0.023 m²K/W
Show the working
  1. Rsi (inside surface): 0.13 m²K/W
  2. Brick: 102.5 mm ÷ 0.77 W/mK = 0.133 m²K/W
  3. PIR: 100 mm ÷ 0.022 W/mK = 4.545 m²K/W
  4. Aircrete block: 100 mm ÷ 0.15 W/mK = 0.667 m²K/W
  5. Plaster: 13 mm ÷ 0.57 W/mK = 0.023 m²K/W
  6. Rse (outside surface): 0.04 m²K/W
  7. Total R: 5.538 m²K/W
  8. U-value: 1 ÷ 5.538 = 0.181 W/m²K

How it works

  1. Each layer's resistance R = thickness d (m) ÷ thermal conductivity λ (W/mK)
  2. Total resistance R = Rsi + Σ R + Rse; U-value = 1 ÷ R (W/m²K)
  3. Bridged layer (studs or joists): the average of the upper and lower limits of R, from the share of the layer taken by the timber (BS EN ISO 6946 combined method)
  4. The check uses the unrounded U-value, so 0.181 is over a 0.18 limit even though it shows as 0.18 to 2 decimal places

Corrections for air gaps, wall ties and fixings (ΔU) are not included, and cavities and ground floors aren't modelled: the insulation maker can give a full calculation.

Material λ values are still being checked: use the maker's declared λ.

Our default (adjustable)

These are typical planning figures and our own allowances, not facts about your product. Change any of them in the calculator to match your bag, pack or tin.

FigureOur default (adjustable)KindSource
Inside surface resistance Rsi: Wall0.13 m²K/WOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Inside surface resistance for a wall (horizontal heat flow) as used in brief v2 I1 test UV1 (BS EN ISO 6946). Researcher to cite the clause.
Outside surface resistance Rse: Wall0.04 m²K/WOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Outside surface resistance for a wall as used in brief v2 I1 test UV1 (BS EN ISO 6946). Researcher to cite the clause.
Inside surface resistance Rsi: RoofEnter from the bag, pack or tinOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Brief v2 I1: Rsi by element (BS EN ISO 6946), upward heat flow. Not stated in the brief; Researcher to fill.
Outside surface resistance Rse: RoofEnter from the bag, pack or tinOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Brief v2 I1: Rse by element (BS EN ISO 6946). Not stated for roofs in the brief; Researcher to fill.
Inside surface resistance Rsi: FloorEnter from the bag, pack or tinOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Brief v2 I1: Rsi by element (BS EN ISO 6946), downward heat flow. Not stated in the brief; Researcher to fill.
Outside surface resistance Rse: FloorEnter from the bag, pack or tinOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Brief v2 I1: Rse by element (BS EN ISO 6946). Not stated for floors in the brief; Researcher to fill (ground floors are treated differently, BS EN ISO 13370).

Regulations and standards

  • Approved Document L 2021 Vol 1, Table 4.2 (new elements) and Table 4.3 (renovated elements), England
  • BS EN ISO 6946 (U-value method)

Explained: Approved Document L (conservation of fuel and power), BS EN ISO 6946 (U-values).

Our Part L figures are for England. Wales, Scotland and Northern Ireland set their own limits, which we're still adding.

Reference tables this calculator reads
TableClauseNationsStatus
Thermal conductivity (λ) of common materialsBS EN ISO 10456 design values / maker data sheets (Researcher to cite per row)UK-wide0/12 values entered
Not yet checked against the source
Part L limiting U-values by nation, element and workApproved Document L 2021 Vol 1 (England); Wales, Scotland and Northern Ireland equivalents (Researcher)UK-wide3/36 values entered
Not yet checked against the source